# A/C evacuation and vacuum retention check (2001–2004)

Canonical URL: https://miatatorque.com/spec/ac-evacuation-vacuum-retention-2003-2004/

Applicability: NB 2003 (BP-Z3); NB 2004 (BP-Z3); NB 2001–2002 (BP-Z3) — 2001–2002 applicability follows the owner-approved early-NB2 mechanical carry-over policy, checked against coverless publication 1719-1U-01G. Its exact edition/market remains unconfirmed; this does not establish independently verified model years.

Confidence: fsm

Run the vacuum pump for 15 minutes; both manifold gauges at –101 kPa {–760 mmHg, –29.9 inHg}. Close all manifold valves, stop the pump and wait about 5 minutes; the low-side reading must remain unchanged.

Always confirm against your factory manual. Match every restriction and follow all stages and procedure notes. Disputed claims must not be automatically resolved. The complete record below preserves every printed unit, source claim and procedure.

```json
{
  "id": "ac-evacuation-vacuum-retention-2003-2004",
  "name": "A/C evacuation and vacuum retention check (2001–2004)",
  "aliases": [],
  "applies_to": [
    {
      "gen": "NB",
      "years": [
        2003,
        2003
      ],
      "engines": [
        "BP-Z3"
      ]
    },
    {
      "gen": "NB",
      "years": [
        2004,
        2004
      ],
      "engines": [
        "BP-Z3"
      ]
    },
    {
      "gen": "NB",
      "years": [
        2001,
        2002
      ],
      "engines": [
        "BP-Z3"
      ],
      "note": "2001–2002 applicability follows the owner-approved early-NB2 mechanical carry-over policy, checked against coverless publication 1719-1U-01G. Its exact edition/market remains unconfirmed; this does not establish independently verified model years."
    }
  ],
  "kind": "non-torque",
  "value_text": "Run the vacuum pump for 15 minutes; both manifold gauges at –101 kPa {–760 mmHg, –29.9 inHg}. Close all manifold valves, stop the pump and wait about 5 minutes; the low-side reading must remain unchanged.",
  "procedure": {
    "notes": "Original R-134a system. Use R-134a recovery/recycling/recharging equipment and recover refrigerant before opening the system. Install the manifold gauge set with both side valves closed before connecting the high/low service couplers. Connect the vacuum pump to the manifold center joint, and the tap-pin side of the charging hose to its air-purge valve. Connect the tank to the charging hose and place it on a scale, keeping the tank supply closed for evacuation. Open the manifold valves and operate the vacuum pump. After the stated time and gauge readings, close each manifold valve before stopping the pump. Wait about five minutes and inspect the low-side reading. If it changes, check for leaks and repeat evacuation. If unchanged, proceed to the separate preliminary refrigerant leak check. These are signed manifold gauge readings, not absolute pressure."
  },
  "confidence": "fsm",
  "sources": [
    {
      "source": "fsm-2003",
      "page": "Refrigerant charging (PDF p. 1613)",
      "as_printed": "Start the vacuum pump and let it operate for 15 minutes.",
      "verified_years": [
        2003,
        2003
      ],
      "document": {
        "id": "fsm-2003",
        "tier": 1,
        "title": "2003 Mazda MX-5 Miata Workshop Manual (electronic manual capture)",
        "covers": [
          {
            "gen": "NB",
            "years": [
              2003,
              2003
            ],
            "engines": [
              "BP-Z3"
            ]
          }
        ],
        "note": "Normally aspirated BP procedures audited; turbo procedures are covered separately."
      }
    },
    {
      "source": "fsm-2004",
      "page": "Refrigerant charging (PDF p. 1609)",
      "as_printed": "Start the vacuum pump and let it operate for 15 minutes.",
      "verified_years": [
        2004,
        2004
      ],
      "document": {
        "id": "fsm-2004",
        "tier": 1,
        "title": "2004 Mazda MX-5 Miata Workshop Manual (electronic manual capture)",
        "covers": [
          {
            "gen": "NB",
            "years": [
              2004,
              2004
            ],
            "engines": [
              "BP-Z3"
            ]
          }
        ],
        "note": "Normally aspirated BP procedures audited; turbo procedures are covered separately."
      }
    },
    {
      "source": "fsm-2003",
      "page": "Refrigerant charging (PDF p. 1614)",
      "as_printed": "Verify that the high and low-pressure side readings of the manifold gauge are at –101 kPa {–760 mmHg, –29.9 inHg}. Close each valve of the manifold gauge.\nStop the vacuum pump and wait for about 5 minutes.",
      "verified_years": [
        2003,
        2003
      ],
      "document": {
        "id": "fsm-2003",
        "tier": 1,
        "title": "2003 Mazda MX-5 Miata Workshop Manual (electronic manual capture)",
        "covers": [
          {
            "gen": "NB",
            "years": [
              2003,
              2003
            ],
            "engines": [
              "BP-Z3"
            ]
          }
        ],
        "note": "Normally aspirated BP procedures audited; turbo procedures are covered separately."
      }
    },
    {
      "source": "fsm-2004",
      "page": "Refrigerant charging (PDF p. 1610)",
      "as_printed": "Verify that the high and low-pressure side readings of the manifold gauge are at –101 kPa {–760 mmHg, –29.9 inHg}. Close each valve of the manifold gauge.\nStop the vacuum pump and wait for about 5 minutes.",
      "verified_years": [
        2004,
        2004
      ],
      "document": {
        "id": "fsm-2004",
        "tier": 1,
        "title": "2004 Mazda MX-5 Miata Workshop Manual (electronic manual capture)",
        "covers": [
          {
            "gen": "NB",
            "years": [
              2004,
              2004
            ],
            "engines": [
              "BP-Z3"
            ]
          }
        ],
        "note": "Normally aspirated BP procedures audited; turbo procedures are covered separately."
      }
    },
    {
      "source": "workshop-1719-1u-01g",
      "page": "07–10–4 (PDF p. 741)",
      "as_printed": "Start the vacuum pump and let it operate for 15 minutes.\nVerify that the high- and low-pressure side readings of the manifold gauge are at –101 kPa {–760 mmHg, –29.9 inHg}. Close each valve of the manifold gauge.\nStop the vacuum pump and wait for about 5 minutes.\nIf the reading has changed, check for leaks and then repeat from step 7.",
      "note": "Visually checked against the original page. Early-NB2 mechanical use authorized by owner; exact full-document edition and market remain unconfirmed.",
      "document": {
        "id": "workshop-1719-1u-01g",
        "tier": 1,
        "title": "Mazda MX-5 Workshop Manual, publication 1719-1U-01G (2002 base edition)",
        "part_number": "1719-1U-01G",
        "covers": [
          {
            "gen": "NB",
            "years": [
              2002,
              2002
            ],
            "engines": [
              "BP-Z3"
            ]
          }
        ],
        "note": "Factory typeset document supplied in the purchased 2001–2005 package; 1,009 PDF pages. Running headers dated June 2001, A5U procedure identifiers. The copy omits its title/model-year cover. The owner accepted it as the tier-1 source for NB 2002 (BP-Z3) on 2026-10-23; it claims no coverage of 2001, later years or Mazdaspeed. A 2026-10-22 census finds the same 1719 running header on all 1,009 pages across 84 section files. Normalized extracted text exactly matches the archived 2002 samples at PDF pages 268 (timing belt), 526 (front brake), 925 (interior trim) and 931 (lighting). This supports a likely 2002 base-edition identity, but does not establish every page revision, regional applicability or a 2001–2005 coverage range. See docs/NB2-MANUAL-IDENTIFICATION.md for evidence and remaining checks. Reviewed HVAC pages corroborate the existing DENSO OIL9 records."
      }
    }
  ],
  "jobs": [],
  "system": "hvac",
  "component": "combined-audit-2026-10",
  "componentName": "Factory hvac service audit",
  "sequence_diagrams": [],
  "url": "https://miatatorque.com/spec/ac-evacuation-vacuum-retention-2003-2004/"
}
```