# A/C evacuation and vacuum retention (2004–2005)

Canonical URL: https://miatatorque.com/spec/ac-evacuation-vacuum-retention-2005/

Applicability: NB 2005 (BP-Z3/BP-Z3-TURBO); NB 2004 (BP-Z3-TURBO) — 2005 Mazdaspeed applicability is supported by the cited 2005 factory pages; 2004 Mazdaspeed follows the owner-approved 2004–2005 Mazdaspeed carry-over policy. No 2004 Mazdaspeed revision verification is claimed.

Confidence: fsm

Run the vacuum pump for 15 minutes; both manifold gauges at –101 kPa {–760 mmHg, –29.9 inHg}. Close all manifold valves, stop the pump and wait about 5 minutes; the low-side reading must remain unchanged.

Always confirm against your factory manual. Match every restriction and follow all stages and procedure notes. Disputed claims must not be automatically resolved. The complete record below preserves every printed unit, source claim and procedure.

```json
{
  "id": "ac-evacuation-vacuum-retention-2005",
  "name": "A/C evacuation and vacuum retention (2004–2005)",
  "aliases": [],
  "applies_to": [
    {
      "gen": "NB",
      "years": [
        2005,
        2005
      ],
      "engines": [
        "BP-Z3",
        "BP-Z3-TURBO"
      ]
    },
    {
      "gen": "NB",
      "years": [
        2004,
        2004
      ],
      "engines": [
        "BP-Z3-TURBO"
      ],
      "note": "2005 Mazdaspeed applicability is supported by the cited 2005 factory pages; 2004 Mazdaspeed follows the owner-approved 2004–2005 Mazdaspeed carry-over policy. No 2004 Mazdaspeed revision verification is claimed."
    }
  ],
  "kind": "non-torque",
  "value_text": "Run the vacuum pump for 15 minutes; both manifold gauges at –101 kPa {–760 mmHg, –29.9 inHg}. Close all manifold valves, stop the pump and wait about 5 minutes; the low-side reading must remain unchanged.",
  "procedure": {
    "notes": "Original R-134a system. Use R-134a recovery/recycling/recharging equipment and recover refrigerant before opening the system. Install the manifold gauge set with both side valves closed before connecting the high/low service couplers. Connect the vacuum pump to the manifold center joint, and the tap-pin side of the charging hose to its air-purge valve. Connect the tank to the charging hose and place it on a scale, keeping the tank supply closed for evacuation. Open the manifold valves and operate the vacuum pump. After the stated time and gauge readings, close each manifold valve before stopping the pump. Wait about five minutes and inspect the low-side reading. If it changes, check for leaks and repeat evacuation. If unchanged, proceed to the separate preliminary refrigerant leak check. These are signed manifold gauge readings, not absolute pressure."
  },
  "confidence": "fsm",
  "sources": [
    {
      "source": "fsm-2005",
      "page": "Refrigerant Charging (PDF pp.1741–1742)",
      "as_printed": "Start the vacuum pump and let it operate for 15 min.\nVerify that the high and low-pressure side readings of the manifold gauge are at –101 kPa {–760 mmHg, –29.9 inHg}. Close each valve of the manifold gauge.\nStop the vacuum pump and wait for about 5 min.\nIf the reading has changed, check for leaks and then repeat from Step 7.",
      "verified_years": [
        2005,
        2005
      ],
      "document": {
        "id": "fsm-2005",
        "tier": 1,
        "title": "2005 Mazda MX-5 Miata Workshop Manual (electronic manual capture)",
        "covers": [
          {
            "gen": "NB",
            "years": [
              2005,
              2005
            ],
            "engines": [
              "BP-Z3"
            ]
          },
          {
            "gen": "NB",
            "years": [
              2005,
              2005
            ],
            "engines": [
              "BP-Z3-TURBO"
            ],
            "trans": [
              "6MT"
            ]
          }
        ]
      }
    }
  ],
  "jobs": [],
  "system": "hvac",
  "component": "release-validation-2005-2026-11",
  "componentName": "Factory HVAC service references (2005)",
  "sequence_diagrams": [],
  "url": "https://miatatorque.com/spec/ac-evacuation-vacuum-retention-2005/"
}
```